Javascript is required
1.
J. Wang, H. Li, and Y. Peng, “Application models of renewable energy under the carbon neutrality target,” Mod. Ch., vol. 42, no. 5, pp. 6-6, 2022. [Google Scholar]
2.
Y. Z. Wang, L. Kang, and J. Zhang, “Development history, typical form and future trend of integrated energy system,” Act. Energiae Solaris Sinica, vol. 42, no. 8, pp. 84-95, 2021. [Google Scholar]
3.
F. Cao, T. Guo, and A. Yin, “Research progress on design and energy management strategies of wind-solar-hydrogen hybrid power generation systems,” Distrib. Energy, vol. 6, no. 4, pp. 1-14, 2021. [Google Scholar]
4.
G. Cai, C. Chen, and L. Kong, “Modeling and control of wind power/photovoltaic/hydrogen production/supercapacitor grid-connected system,” Pow. Sys. Technol., vol. 40, no. 10, pp. 2982-2990, 2016. [Google Scholar]
5.
H. Kinoshita, R. Takahashi, T. Murata, J. Tamura, M. Sugimasa, A. Komura, and K. Ide, “A study of hydrogen generation with doubly-fed adjustable speed wind generator,” Electr. Eng. Jpn., vol. 175, no. 3, pp. 27-36, 2011. [Google Scholar] [Crossref]
6.
A. Abdelkafi and L. Krichen, “Energy management optimization of a hybrid power production unit based renewable energies,” Int. J. Elec. Power. Energy Syst., vol. 62, pp. 1-9, 2014. [Google Scholar] [Crossref]
7.
Y. Lu, C. Chen, and L. Liang, “Modeling and control of wind-hydrogen coupled system based on electric-hydrogen hybrid energy storage,” Mag. Introduct., vol. 48, no. 3, pp. 8-8, 2020. [Google Scholar]
8.
H. Zhang, Q. Sun, and Z. Li, “Research on cooperative control power generation strategy of wind-hydrogen coupling system,” J. Northeast Dian li Univ., vol. 38, no. 3, pp. 15-23, 2018. [Google Scholar]
9.
R. Maamouri, D. Guilbert, M. Zasadzinski, and H. Rafaralahy, “Proton exchange membrane water electrolysis: Modeling for hydrogen flow rate control,” Int. J. Hydrogen. Energ., vol. 46, no. 11, pp. 7676-7700, 2021. [Google Scholar] [Crossref]
10.
H. Deng, J. Chen, and Y. Teng, “Research on energy management strategy of wind-hydrogen coupling system,” Act. Energiae Solaris Sinica, vol. 42, no. 1, pp. 256-263, 2021. [Google Scholar]
11.
H. Sun, Z. Li, and A. Chen, “Status quo and development trend of wind power hydrogen production technology,” T. China Electrotechnical Soc., vol. 34, no. 19, pp. 4071-4083, 2019. [Google Scholar]
12.
H. Deng, J. Chen, and D. Jiao, “Energy management control strategy of wind-hydrogen coupled grid-connected system,” High Voltage Eng., vol. 8, no. 1, pp. 99-106, 2020. [Google Scholar]
13.
J. Wang, H. Li, and Y. Peng, “PEMFC modeling and performance analysis control,” Elect. Meas. Technol., vol. 45, no. 8, pp. 8-8, 2022. [Google Scholar]
14.
X. Guo, Y. Wei, and Y. Wan, “Overview of new energy hydrogen production power electronic converters,” Automat. Electr. P. Sys., vol. 45, no. 20, pp. 15-15, 2021. [Google Scholar]
15.
L. Kong, “Research on optimal configuration and coordinated control strategy of wind-solar-hydrogen integrated energy system,” Academic Dissertation, North China Electric Power University, Beijing, China, 2017. [Google Scholar]
16.
M. S. Fathy, H. Awad, H. Hegarzy, and E. E. Elkholy, “Performance of a PV-wind hybrid system under severe weather and loading conditions,” Int. J. Ind. Elec. Drive., vol. 4, no. 3, pp. 145-154, 2018. [Google Scholar] [Crossref]
17.
E. Ribeiro, A. J. M. Cardoso, and C. Boccaletti, “Power converters analysis in a renewable energy based hybrid system with hydrogen storage,” In IET Conference on Renewable Power Generation, (RPG 2011), Edinburgh, September 6-8, 2011, IET, pp. 1-6. [Google Scholar] [Crossref]
18.
J. P. Torreglosa, P. García, L. M. Fernández, and F. Jurado, “Energy dispatching based on predictive controller of an off-grid wind turbine/photovoltaic/hydrogen/battery hybrid system,” Renew. Energ., vol. 74, pp. 326-336, 2015. [Google Scholar] [Crossref]
19.
Z. Abdin and W. Mérida, “Hybrid energy systems for off-grid power supply and hydrogen production based on renewable energy: A techno-economic analysis,” Energ. Convers. Manage., vol. 196, pp. 1068-1079, 2019. [Google Scholar] [Crossref]
20.
A. O. Haruni, M. Negnevitsky, M. E. Haque, and A. Gargoom, “A novel operation and control strategy for a standalone hybrid renewable power system,” IEEE T. Sustain. Energ., vol. 4, no. 2, pp. 402-413, 2012. [Google Scholar] [Crossref]
Search
Open Access
Research article

Modeling and Control Strategy of Wind-Solar Hydrogen Storage Coupled Power Generation System

tianze yuan,
hua li*,
dong jia
School of Energy and Power Engineering, Inner Mongolia University of Technology, 010051 Hohhot, China
Journal of Intelligent Systems and Control
|
Volume 1, Issue 1, 2022
|
Pages 18-34
Received: 06-12-2022,
Revised: 07-17-2022,
Accepted: 07-29-2022,
Available online: 10-29-2022
View Full Article|Download PDF

Abstract:

Hydrogen production by wind and solar hybrid power generation is an important means to solve the strong randomness and high volatility of wind and solar power generation. In this paper, the permanent magnet direct-drive wind turbine, photovoltaic power generation unit, battery pack, and electrolyzer are assembled in the AC bus, and the mathematical model of the wind-solar hydrogen storage coupled power generation system and the simulation model in PSCAD/EMTDC are established. An energy coordination control strategy is designed. After simulation, the proposed control strategy can effectively reduce the rate of curtailment of wind and solar power, and stabilize the fluctuation of wind and solar power generation. It verifies that the established model is correct and the control strategy is effective and feasible.

Keywords: Wind-solar hybrid, Hydrogen energy, Wind-solar hydrogen storage, Control strategy, Modeling

1. Introduction

In recent years, the environmental problems caused by the large-scale use of fossil energy are becoming more and more serious And, fossil energy is a non-renewable energy, the massive use of fossil energy has gradually brought about a global energy crisis. New energy power generation technology has the advantages of clean and renewable [1], the research on new energy power generation technology has been widely concerned and highly valued by countries all over the world. Wind energy and solar energy are the two main technologies for new energy power generation, however, due to the strong randomness and volatility of wind and solar energy, high rate of abandonment of wind and light. Consume excess wind power and photovoltaics by electrolyzing water to produce hydrogen, and use batteries to make up for the lack of wind power and photovoltaic power generation is an important meansto solve the strong volatility of wind power and photovoltaic power generation [2].

There have been many studies on hydrogen production from wind power and photovoltaics. Reference [3] reviewed the system composition and energy management strategies of wind-solar-hydrogen coupled power generation. Cai et al. [4] proposes a grid-connected power generation system in which wind power, photovoltaics, hydrogen production, and supercapacitors are assembled on the DC bus, and proposes corresponding control strategies according to four operating scenarios, which can suppress short-term wind and light energy fluctuations and reduce waste. Kinoshita et al. [5] proposed to electrolyze the excess power of wind power to produce hydrogen, which greatly reduces the wind curtailment rate, but the control strategy of the electrolyzer switch limits the power generation efficiency of the wind farm. Abdelkafi and Krichen [6] proposes a power generation system that combines wind power to produce hydrogen with fuel cells and supercapacitors, and adjusts the power generation according to the energy storage level to adapt to the load. This control strategy significantly improves the power generation efficiency and reliability of the system. Lu et al. [7] proposes an energy management strategy for a wind-hydrogen coupled power generation system, which uses the fast response capability of supercapacitors to make up for the shortcomings of the slow response speed of electrolyzers and fuel cells. Zhang et al. [8] proposes an energy coordinated control strategy for wind-hydrogen coupled power generation under three operating conditions, and introduces super capacitors to reduce the voltage change at the grid connection point, which verifies the effectiveness of its control strategy. Maamouri et al. [9] studied the proton exchange membrane electrolyzer and its converter, and proposed a control method of electrolyzer operation, and verified its control strategy through simulation.

The above studies are mainly focused on wind power hydrogen production systems, and most studies use supercapacitors to make up for short-term power shortages [10]. In order to make full use of wind energy and solar energy and stabilize long-term wind and wind fluctuations, this paper constructs a structure in which permanent magnet direct-drive wind turbines, photovoltaic power generation units, storage batteries, and proton exchange membrane electrolyzers are collected on the AC bus through the converter. This paper firstly establishes the mathematical model of each module in PSCAD/EMTDC software, and considers the hydrogen storage state of the hydrogen storage tank and the output characteristics of the battery, and designs a set of energy management strategies for the coupling system of wind power, photovoltaic, hydrogen production and energy storage and its various the module inverter control strategy makes the output of each module complementary and controllable, and stabilizes the fluctuation of wind and solar output. Finally, the effectiveness and feasibility of the control strategy are verified by simulation.

2. Model Building

2.1 Wind Turbine Modeling

A wind turbine is a component in a wind power system that converts wind energy into mechanical energy, the wind power equation is [11]:

$P_w=\frac{1}{2} A \rho v_w^3 C_p(\lambda, \theta)$
(1)

In the above formula: Pw is the mechanical power extracted from the wind turbine; Cp is the power coefficient with respect to λ and θ; λ is the tip speed ratio; θ is the pitch angle; A is the area (m2) covered by the blades of a wind turbine as they rotate; ρ is the air density; vw is wind speed.

First, the dq coordinate system is constructed. The central axis of the magnetic field N pole generated by the rotor magnetic pole of the synchronous motor is taken as the d axis, and the position of the electric angle 90° ahead of the straight axis is defined as the q axis. The intersection of the two axes is the origin of dq coordinate system. In the dq coordinate system, the voltage equation of the permanent magnet synchronous generator (PMSG) is [12], [13]:

$\left\{\begin{array}{l}U_{w d}=-R_{\mathbf{s}^i d}-L_d \frac{d i d}{d t}+\omega_s L_q{ }^i q \\ U_{w q}=-R_{\mathbf{s}^i d}-L_q \frac{d i q}{d t}-\omega_s L_{d^i d}+\omega_s \Psi_f\end{array}\right.$
(2)

The shafting model of PMSG is:

$J \frac{d \omega_m}{d t}=T_m-T_e-B \omega_m$
(3)

In the above formula: Tm is the mechanical torque of the fan; Te is the electromagnetic torque; J is the moment of inertia of the permanent magnet machine rotor; ωm is the wind turbine speed; B is the viscosity coefficient.

2.2 Modeling of Photovoltaic Power Generation Units

The mathematical model of photovoltaic power generation unit is:

$I=N_p I_{S C} \cdot\left\{1-C_1\left[\exp \left(\frac{U-d U}{C_2 N_S U_{O C}}\right)-1\right]\right\}+d I$
(4)

In the formula:

$C_1=\left(1-\frac{I_m}{I_{S c}}\right) \cdot \exp \left(-\frac{U_m}{C_2 U_{o c}}\right)$
(5)
$C_2=\frac{\frac{U_m}{U_{o c}}-1}{\ln \left(1-\frac{I_m}{I_{s c}}\right)}$
(6)
$d I=-\alpha \frac{G}{G_{r e f}}\left(T_e-T_{r e f}\right)+\left(\frac{G}{G_{r e f}}-1\right) \cdot N_p I_{s c}$
(7)
$d U=\beta d T-R_s d I$
(8)
$T_e=T_a+t_c G$
(9)

In the above formula: Uoc is the open circuit voltage of photovoltaic modules; Isc is the short-circuit current of photovoltaic modules; Um is the maximum power point voltage of photovoltaic modules; Im is the maximum power point current of the photovoltaic module; G is the solar radiation intensity; α is the current temperature variation coefficient; β is the voltage temperature variation coefficient; Ta is the ambient temperature; tc is the temperature variation coefficient of photovoltaic modules; Rs is the series resistance of the component; Np is the parallel number of modules in the PV array; NS is the serial number of modules in the PV array.

2.3 Battery Modeling

The battery mathematical model is:

$E=N_s E_0-\frac{K S O C}{S O C-N_s Q_n \int_0^t i(\tau) d \tau}+E_t$
(10)

In the formula:

$S O C=\frac{N_s N_p Q_n-\int_0^t i(\tau) d \tau}{N_s N_p Q_n} \times 100 \%$
(11)
$E_t=A \exp \left(-B \int_0^t i(\tau) \mathrm{d} \tau+\mathrm{C}_b\right)$
(12)
$C_b=C_t\left(T_b-25\right)$
(13)

In the above formula: E0 is the initial potential; K is the polarization voltage constant; Ns is the number of batteries in series; Np is the number of parallel battery packs; A is the voltage variation coefficient; B is the capacity change coefficient; Qn is the rated capacity of the battery; SOC is the state of charge; i(t) is the charge and discharge current; C(t) is the polarization effect coefficient; Tb is the battery temperature.

2.4 Electrolyzer Model

This paper chooses to model the Proton Exchange Membrane Electrolysis (PEMEL) cell. Proton exchange membrane electrolyzer has high current density, good safety of alkaline free solution, rapid startup and shutdown, high hydrogen production purity, and a certain overload range. It can be used in combination with natural random wind power and photoelectric. The PEMEL mathematical model is [14]:

$\left\{\begin{array}{l}V_{\text {ele }}=E_{\text {ele }}+V_{\text {el,act }}+V_{\text {el,ohm }} \\ E_{\text {ele }}=\frac{\Delta G_f}{2 F}+\frac{R T_{e l}}{2 F}\left[\ln \left(\frac{P_{H_2} P_{O_2}{ }^{\frac{1}{2}}}{a_{H_2 O}}\right)\right] \\ V_{\text {el,act }}=\frac{R T_{e l}}{2 \alpha F} \ln \left(\frac{i}{i_0}\right) \\ V_{\text {el,ohm }}=i R_{\text {el,ohm }}=\frac{t_m}{\sigma_m} \\ \sigma_m=\left(0.00514 \lambda_m-0.00326\right) \exp \left(1268\left(\frac{1}{303}-\frac{1}{T_{e l}}\right)\right)\end{array}\right.$
(14)

In the above formula: Vele is the cell voltage; Eele is the open circuit voltage; Vel,act is the activation polarization voltage; Vel.ohm is the ohmic polarization voltage; F is Faraday's constant; R is the gas constant; Gf  is Gibbs free energy; Tel is the temperature of the electrolytic cell; λm is the water content of the membrane; i is the current density; i0 is the exchange current density; σ is the membrane conductivity; α is the transfer coefficient.

The hydrogen production rate of the electrolyzer is:

$\left\{\begin{array}{l}v_{H_2}=\eta\left(T_{e l}, j\right) \frac{N_{e l}}{2 F} I_{e l} \\ \eta\left(T_{e l}, j\right)=a_1 \exp \left(\frac{a_2+a_3 T_{e l}}{j}+\frac{a_4+a_5 T_{e l}}{j^2}\right)\end{array}\right.$
(15)

In the above formula: vH2 is the hydrogen production rate; j is the current density; Iel is the electrolyzer current; ɑ is the Faraday efficiency coefficient; Nel is the number of electrolyzers in series.

2.5 Hydrogen Storage Tank Modeling

In this paper, the high-pressure gas pipe is used to store hydrogen, and the hydrogen storage tank is modeled from the aspects of hydrogen storage capacity and gas tank pressure. The mathematical model of the hydrogen storage tank is:

$\left\{\begin{array}{l}M_{H_2}=\int_{t_1}^{t_2} v_{H_2} d t+n_s\left(t_0\right) \\ P_s=\frac{R T_s}{V_s}\left(M_{H_2}\right)\end{array}\right.$
(16)

In the above formula: Ps is the pressure of the hydrogen storage tank; MH2 is the hydrogen storage capacity of the hydrogen storage tank; Ts is the temperature of the hydrogen storage tank; R is the gas constant; ns(t0) is the hydrogen storage amount at t0; Vs is the volume of the hydrogen storage tank; t1 and t2 are the beginning and end time of hydrogen storage and hydrogen intake.

3. System Coordination Control

The structure of the wind-solar hydrogen storage coupled power generation system is shown in the Figure 1. Wind turbines, photovoltaic arrays, batteries, and electrolyzers are collected on the AC bus through the converter, and then the electric energy is fed into the power grid through the AC bus. The hydrogen produced by the electrolyzer is fed into the hydrogen storage tank through the pipeline for nearby hydrogen energy loads. The system utilizes the surplus power generation when wind and light are abundant to produce hydrogen, reducing the rate of abandoning wind and light. The battery pack is responsible for supplementing the lack of power when wind and photovoltaic power generation is insufficient, and absorbing part of the surplus wind power and photovoltaics. The battery pack is connected to the AC bus through the inverter, which is composed of bidirectional DC converter and grid connected inverter.

3.1 Energy Control

The system power balance objective function is:

$\left\{\begin{array}{l}P_{w p}+P_{b a t}=P_{l d}+P_{e l} \\ P_{w p}=P_{\text {wind }}+P_{p v}\end{array}\right.$
(17)

In the above formula, Pwind is wind turbine output power; Ppv is output power for PV array; Pbat is charging and discharging power for battery; Pld is demand power for grid loads; Pel is Power consumption for the electrolyzer; Pwp is the sum of the output power of wind and photovoltaic power generation units. In addition to considering the rated power of each unit to limit its output, this paper also considers the battery state of charge, the terminal voltage limit, and the upper and lower limits of the hydrogen storage tank pressure.

The constraints of battery operation are:

$\left\{\begin{array}{l}U_{\min } \leq U_{b a t} \leq U_{\max } \\ 15 \% \leq S O C \leq 90 \%\end{array}\right.$
(18)

In the above formula, Ubat is the battery terminal voltage; Umin is the lower limit of the battery terminal voltage; Umax is the upper limit of the battery terminal voltage; SOC is the battery state of charge.

The operating constraints of the hydrogen storage tank are:

$P_{\min } \leq P_{\text {tan }} \leq P_{\max }$
(19)

In the above formula, Ptan is the pressure of the hydrogen storage tank; Pmin is the lower limit of the pressure of the hydrogen storage tank; Pmax is the upper limit of the pressure of the hydrogen storage tank.

The system power coordination control method is shown in Figure 2. The energy management strategy in this paper is divided into 13 working conditions.

Figure 1. Structure of wind-solar hydrogen storage coupled power generation system
Figure 2. System power coordination control

(1). When the output power of wind power and photoelectric power is greater than or equal to the grid side load; The pressure of hydrogen storage tank is less than the upper pressure limit; The rated power of the electrolytic cell is greater than that of wind power and photoelectric power; And make the reference power of the electrolytic cell equal to the power generated by wind power and photoelectric less the grid side load.

(2). When the output power of wind power and photoelectric power is greater than or equal to the grid side load; The pressure of hydrogen storage tank is greater than the upper pressure limit; The rated power of electrolytic cell shall not be greater than the power generated by wind power and photoelectric power; The terminal voltage of the storage battery is greater than or equal to the upper voltage limit; The reference power of the storage battery is 0, and the reference power of the electrolytic cell is equal to the rated power.

(3). When the output power of wind power and photoelectric power is greater than or equal to the grid side load; The pressure of hydrogen storage tank is greater than the upper pressure limit; The rated power of electrolytic cell shall not be greater than the power generated by wind power and photoelectric power; The terminal voltage of storage battery is less than the upper limit of voltage; The rated power of the battery pack is greater than that of the wind power and photoelectric power minus the grid side load power minus the rated power of the electrolytic cell; The reference power of the storage battery is equal to the wind power and photoelectric power minus the grid side load power minus the rated power of the electrolytic cell, and the reference power of the electrolytic cell is equal to the rated power.

(4). When the output power of wind power and photoelectric power is greater than or equal to the grid side load; The pressure of hydrogen storage tank is greater than the upper pressure limit; The rated power of electrolytic cell shall not be greater than the power generated by wind power and photoelectric power; The terminal voltage of storage battery is less than the upper limit of voltage; The rated power of the storage battery shall not be greater than that of the wind power and photoelectric power minus the grid side load power minus the rated power of the electrolytic cell; Make the reference power of the battery pack equal to the rated power of the battery pack and the reference power of the electrolytic cell equal to the rated power.

(5). When the output power of wind power and photoelectric power is greater than or equal to the grid side load; The pressure of hydrogen storage tank is greater than the upper pressure limit; The terminal voltage of the storage battery is greater than or equal to the upper voltage limit; The reference power of the electrolytic cell is 0 and the reference power of the storage battery is 0.

(6). When the output power of wind power and photoelectric power is greater than or equal to the grid side load; The pressure of hydrogen storage tank is greater than the upper pressure limit; The terminal voltage of storage battery is less than the upper limit of voltage; The rated power of the storage battery is greater than that of the wind power and photoelectric power minus the load power at the grid side; The reference power of the battery is equal to the power generated by wind power and photoelectric power minus the grid side load power, and the reference power of the electrolytic cell is 0.

(7). When the output power of wind power and photoelectric power is greater than or equal to the grid side load; The pressure of hydrogen storage tank is greater than the upper pressure limit; The terminal voltage of storage battery is less than the upper limit of voltage; The rated power of the storage battery is less than or equal to the wind power and photovoltaic power minus the load power at the grid side; Make the reference power of the battery equal to the rated power of the battery.

(8). When the wind power and photoelectric power are less than the grid side load; The pressure of hydrogen storage tank is greater than the lower pressure limit; The terminal voltage of storage battery is less than the lower limit of voltage; Let the reference power of the battery set be 0 and the reference power of the electrolytic cell be 0.

(9). When the output power of wind power and photoelectric power is less than the grid side load; The pressure of hydrogen storage tank is less than or equal to the lower pressure limit; The terminal voltage of the storage battery is greater than or equal to the lower voltage limit; The rated power is less than or equal to the absolute value of the wind power and photovoltaic power minus the grid side power; Make the reference power of the storage battery set equal to the absolute value of the wind power and photovoltaic power minus the grid side power; Make the reference power of electrolytic cell 0.

(10). When the wind power and photoelectric power are less than the grid side load; The pressure of hydrogen storage tank is less than or equal to the lower pressure limit; The terminal voltage of the storage battery is greater than or equal to the lower voltage limit; The rated power is less than or equal to the absolute value of the wind power and photovoltaic power minus the grid side power; Make the reference power of the battery set equal to the rated power of the battery set, and make the reference power of the electrolytic cell 0.

(11). When the output power of wind power and photoelectric power is less than the grid side load; The pressure of hydrogen storage tank is greater than the lower pressure limit; The terminal voltage of the storage battery is less than that of the storage battery; The reference power of the storage battery is 0.

(12). When the wind power and photoelectric power are less than the grid side load; The pressure of hydrogen storage tank is greater than the lower pressure limit; The terminal voltage of the storage battery is less than or equal to that of the storage battery; The rated power of the storage battery is less than or equal to the absolute value of the wind power and photovoltaic power minus the power at the grid side; The reference power of the battery pack is equal to the rated power of the battery pack.

(13). When the wind power and photoelectric power are less than the grid side load; The pressure of hydrogen storage tank is greater than the lower pressure limit; The terminal voltage of the storage battery is greater than that of the storage battery; The rated power of the storage battery is less than or equal to the absolute value of the wind power and photovoltaic power minus the power at the grid side; The reference power of the battery is equal to the absolute value of the wind power and photoelectric power minus the power at the grid side minus the rated power of the electrolytic cell.

Kbat is the battery switch; Kele is the electrolytic cell switch; Ktan is the switch of hydrogen storage tank; Pbat-ref and Pele-ref are the battery reference power and the electrolytic cell reference power respectively; PbatN, PeleN are the rated power of the battery and the rated power of the electrolytic cell, respectively.

3.2 Inverter Control Strategy

The energy management center feeds back the reference value according to the operation of each output unit, and coordinates and controls the output of each unit. The control equation of the inverter on the side of the permanent magnet wind turbine:

$\left\{\begin{array}{l}M_{w q}=\frac{-\left(\mathrm{k}_{p 1}+\frac{\mathrm{k}_{i 1}}{s}\right)\left[\left(\mathrm{k}_{p 2}+\frac{\mathrm{k}_{i 2}}{s}\right)\left(P_{r e f}-P_{g e n}\right)-i_q\right]-i_d \omega_s L_{w d}+\omega_s \Psi_f}{U_{d c}} \\ M_{w d}=\frac{-\left(\mathrm{k}_{p 3}+\frac{\mathrm{k}_{i 3}}{s}\right)\left(i_{d r e f}-i_d\right)+i_q \omega_s L_{w q}}{U_{d c}}\end{array}\right.$
(20)

In the above formula, Mwq is the fan q-axis control pulse; Wdq is the control pulse of the d-axis of the fan; kp and ki are the proportional coefficient and integral coefficient, respectively, and the following are similar; id is the d-axis current; iq is the q-axis current; Pref reference power for wind turbines; Pgen is the actual power of the wind turbine; Lwd is the d-axis filter inductance; Lwq is the q-axis filter inductance; Udc is the DC link voltage. Since the d-axis current is related to reactive power, iderf=0 is set in the control process.

The control equation of the grid-side converter of the permanent magnet fan is:

$\left\{\begin{array}{l}M_{w q 1}=\frac{\left(\mathrm{k}_{p 4}+\frac{\mathrm{k}_{i 4}}{s}\right)\left(i_{q 1 r e f}-i_{q 1}\right)+i_{d 1} \omega L+U_{q 2}}{U_{d c}} \\ M_{w d 1}=\frac{\left(\mathrm{k}_{p 5}+\frac{\mathrm{k}_{i 5}}{s}\right)\left(i_{d 1 r e f}-i_{d 1}\right)+U_{d 2}-i_{q 1} \omega L}{U_{d c}}\end{array}\right.$
(21)

In the formula:

$\left\{\begin{array}{l}i_{d 1 r e f}=\left(\mathrm{k}_{p 6}+\frac{\mathrm{k}_{i 6}}{s}\right)\left(U_{d c r e f}-U_{d c}\right) \\ i_{q 1 \text { lref }}=0\end{array}\right.$
(22)

In the above formula, iq1, id1, Uq2, Ud2 are the components of the grid-side current and voltage on the q-axis and the d-axis, respectively; Mwq1, Mwq1 are the control pulses of the q-axis and d-axis of the grid-side converter of the fan respectively. Since the reactive power output of the grid-side converter can be controlled by controlling the q-axis current, and the DC-side voltage can be stabilized by controlling the d-axis current, the grid-side converter is set to iq1ref=0, and id1ref is obtained from the DC link voltage through the PI controller. The control equation of the photovoltaic unit DC/DC converter is:

$M_{p v}=\frac{\left(\mathrm{k}_{p 7}+\frac{\mathrm{k}_{i 7}}{s}\right)\left(U_{m p p t}-U_{p v}\right)+U_{p v}-U_{d c}}{\left(\mathrm{k}_{p 8}+\frac{\mathrm{k}_{i 8}}{s}\right)\left(U_{m p p t}-U_{p v}\right)+U_{p v}}$
(23)

In the above formula, Umppt is the maximum power tracking voltage of the photovoltaic unit; Upv is the output voltage of the photovoltaic unit; Mpv is the control pulse of the photovoltaic unit.

The control equation of the photovoltaic grid-connected inverter is:

$\left\{\begin{array}{l}M_{p v q}=\frac{\left(\mathrm{k}_{p 9}+\frac{\mathrm{k}_{i 9}}{s}\right)\left(i_{q r e f}-i_q\right)+i_d \omega L}{U_{d c}} \\ M_{p v d}=\frac{\left(\mathrm{k}_{p 10}+\frac{\mathrm{k}_{i 10}}{s}\right)\left(i_{d r e f}-i_d\right)+U_d-i_q \omega L}{U_{d c}}\end{array}\right.$
(24)

In the above formula, iqref, iq, iderf, id are the q-axis current reference value, q-axis current, d-axis voltage reference value, and d-axis current respectively; Mpvq, Mpvd are the trigger pulses of the q-axis and d-axis of the grid-connected inverter of photovoltaic units, respectively. The battery pack adopts a bidirectional DC/DC converter. When the converter is in Buck mode, the control equation is:

$M_{b a t b u c k}=\left[\left(\mathrm{k}_{p 11}+\frac{\mathrm{k}_{i 11}}{s}\right)\left(\frac{P_{\text {inref }}}{i_{b a t}}-U_{b a t}\right) K_2-i_{b a t}\right]\left(\mathrm{k}_{p 12}+\frac{\mathrm{k}_{i 12}}{s}\right)$
(25)

When the converter is in Boost, the control equation is:

$M_{\text {batboost }}=\left[\left(\mathrm{k}_{p 13}+\frac{\mathrm{k}_{i 13}}{s}\right)\left(\frac{P_{\text {outref }}}{i_{b a t}}-U_{d c b a t}\right)-i_{b a t}\right]\left(\mathrm{k}_{p 14}+\frac{\mathrm{k}_{i 14}}{s}\right) K_1$
(26)

In the above formula, Poutref, Pinref are the reference power of battery discharge state and charge state; Ubat is the battery terminal voltage; Udcbat is the DC link voltage of the battery; Mbatbuck is the charging control pulse; Mbatboost is the discharge control pulse. When the battery pack inverter is running in Buck mode, it is charging, and Boost is discharging [15].

The control equation of the grid-connected inverter of the battery pack is:

$\left\{\begin{array}{l}M_{b a t q}=2 \times \frac{U_q-\left(-i_q\right)\left(\mathrm{k}_{p 15}+\frac{\mathrm{k}_{i 15}}{s}\right)+i_d \omega L}{U_{d c b a t}} \\ M_{b a t d}=2 \times \frac{\left[\left(U_{d c b a t r e f}-U_{d c b a t}\right)\left(\mathrm{k}_{p 16}+\frac{\mathrm{k}_{i 16}}{s}\right)-i_d\right]\left(\mathrm{k}_{p 17}+\frac{\mathrm{k}_{i 17}}{s}\right)+U_d+i_q \omega L}{U_{d c}}\end{array}\right.$
(27)

In the above formula, Uq and Ud are the q-axis and d-axis voltages; Mbatq, Mbatd are the control pulses of the q-axis and d-axis of the battery grid-side converter.

The control equation of the DC/DC converter of the electrolyzer is [14]:

$M_{e l}=\left[\left( k _{p 18}+\frac{ k _{i 18}}{s}\right)\left(P_{\text {elref }}-P_{e l}\right)-i_{e l}\right]\left( k _{p 19}+\frac{ k _{i 19}}{s}\right)$
(28)

In the above formula, Mel is the control pulse of the electrolytic cell converter; Pelref and Pel are the reference power and actual power of the electrolyzer respectively; iel is the actual value of the current of the electrolytic cell. The control strategy of the grid-connected inverter of the electrolyzer is the same as that of the grid-connected inverter of the battery, and will not be repeated here.

4. Simulation Study

Build the wind power/photovoltaic/hydrogen production/battery grid-connected power generation system as shown in PSCAD/EMTDC to simulate the weather conditions at dawn, the wind speed is 8m/s in the first 4s, 12m/s in 4s, 8.7m/s in 7s, and 10m/s in 10s and maintained for 15s; In the first 10s, the light intensity was 0W/m2, and the temperature was 28℃, In 10s, the light intensity was changed to 1200W/m2 and kept until 15s, and the temperature remained unchanged. The simulation time is 15s. System parameters see Table 1. Simulation control parameters see Table 2 [16], [17], [18], [19], [20].

According to the scenario set in this paper, the operation of the wind turbine is shown in the Figure 3.

The per-unit value of the fan speed remains 0.48, 1, and 0.63 in the four-stage wind speed change, and the per-unit value of the mechanical torque is 0.6, 1, and 0.8, respectively. The electromagnetic torque follows the mechanical torque fluctuation. The actual output power of the wind turbine is 300kW, 900kW, 400kW, 600kW, the actual output power is similar to the reference power, and the error is within a reasonable range. In this paper, 1MW direct driven fan is selected, which can not only effectively use wind energy but also operate at full load.

The operation of the wind turbine generator side is shown in the Figure 4.

Due to the control strategy in this paper, the d-axis reference current is set to 0. It can be seen from the figure that the d-axis current is basically consistent with the d-axis reference current, and the error is within a reasonable range. The q-axis current fluctuates reasonably with the q-axis reference current when the wind speed changes stepwise.

The operation of the wind turbine grid-side converter is shown in the Figure 5.

The q-axis current and d-axis current of the grid-side converter fluctuate closely with their reference values, and the fluctuation range is less than 0.01kA, which can verify that the control parameters are reasonable. The grid-side DC link is always maintained at around 0.9kV, which is consistent with the reference value of the DC link, which can verify that the grid-side converter is normally turned on.

Table 1. Simulation system device parameters

Device name

Parameter name

Numerical value

PMSG

Rated capacity/kW

1000

Rated wind speed/(m/s)

12

Rated frequency/Hz

50

Air density/(kg/m3)

1.22

Wind turbine radius/m

7.2

Number of pole pairs np

30

Moment of inertia 2H/s

0.02

Viscosity coefficient B(pu)

0.0001

Magnetic field strength(pu)

1.0

PV array

The number of components in series Ns

22

Number of components in parallel Np

250

Current temperature coefficient of variation α/(A/℃)

0.001

Reference light intensity Gref/(W/m2)

1000

Reference temperature Tref/℃

25

Open circuit voltage Uoc/V

45

Short circuit current Ipvsc/A

5.5

Maximum power point voltage Ump/V

36

Maximum power point current Imp/A

5

Voltage Temperature Variation Coefficient β/(V/℃)

0.000 5

Battery pack

Standard/kV

0.6

Rated capacity/(kA h)

100

Capacity loss per hour at nominal current (%)

35

initial state of charge Initial SOC (%)

50

Number of batteries in series

50

Terminal voltage Umax/kV

0.62

Terminal voltage lower limit Umin/kV

0.58

PEMEL

Rated power PeleN/kW

200

Rated current Inom/kA

1.5

Serial number Nel

100

Electrolyzer Tel/K

335

Hydrogen pressure PH2/atm

3

Oxygen pressure PO2/atm

3

Current density i(A/cm2)

0.78

Transfer coefficient α

0.0008

AC current density i0(A/cm2)

0.4

Hydrogen storage tank

Hydrogen storage at timet0 /mol

90000

Hydrogen storage tank volume VS/m3

12

Hydrogen storage tank temperature TS/K

301.15

Upper pressure limit Pmax/Mpa

2.52

Lower pressure limit Pmin/Mpa

2.48

Table 2. Simulation control parameters

Control parameter

Numerical value

Control parameter

Numerical value

PMSG q-axis current control proportional coefficientkp1

10

Battery pack discharge current control integral coefficient kp12

0.01

PMSG q-axis current integral coefficient control ki1

0.02

Battery pack adjustment factor K1

0.08

PMSG active power control kp2

5

Battery pack charging current control proportional coefficient kp13

5

PMSG active power control ki2

0.01

Battery pack charging current control integral coefficient ki13

2

PMSG d-axis current control proportional coefficient kp3

4

Battery pack adjustment factor K2

0.01

PMSG d-axis current control integral coefficientki3

0.04

Battery voltage control proportional coefficient kp14

8

PMSG grid side q-axis current control proportional coefficient kp4

1.5

Battery voltage control integral coefficient ki14

0.02

PMSG grid side q-axis current control integral coefficient ki4

0.01

Battery pack DC voltage control proportional coefficient kp15

4

PMSG grid side d-axis current control proportional coefficient kp5

5

Battery pack DC voltage control integral coefficient ki15

0.025

PMSG grid side d-axis current control integral coefficient ki5

0.01

d-axis current control proportional coefficient kp16 on the battery grid side

10

PMSG DC voltage control proportional coefficient kp6

5

Integral coefficient ki16 for d-axis current control on battery grid side

0.08

PMSG DC voltage control integral coefficient ki6

0.05

q-axis current control proportional coefficient kp17on battery grid side

7

Photovoltaic DC voltage control proportional coefficient kp7

0.5

Integral coefficient ki17 for q-axis current control on battery grid side

0.05

Photovoltaic DC voltage control integral coefficient ki7

0.2

Electrolyzer active power control proportional coefficient kp18

200

Photovoltaic d-axis current control proportional coefficient kp8

0.15

Electrolyzer active power control integral coefficient ki18

0.01

Photovoltaic d-axis current control integral coefficient ki8

0.08

Electrolyzer current control proportional coefficient kp19

0.1

Photovoltaic q-axis current control proportional coefficient kp9

0.15

Electrolyzer current control integral coefficient ki19

0.005

Photovoltaic q-axis current control integral coefficient ki9

0.08

Electrolyzer DC voltage control proportional coefficient kp20

4

Photovoltaic reactive power control proportional coefficient kp10

0.3

Electrolyzer DC voltage control integral coefficient ki20

0.21

Photovoltaic reactive power control integral coefficient ki10

0.02

d-axis current control proportional coefficient kp21on the grid side of the electrolyzer

25

Battery pack DC voltage control proportional coefficient kp11

6

Integral coefficient ki21 for d-axis current control on the grid side of the electrolyzer

0.55

Battery pack DC voltage control integral coefficient ki11

0.03

q-axis current control proportional coefficient kp22on the grid side of the electrolyzer

10

Battery pack discharge current control proportional coefficient ki12

1.5

Integral system of q-axis current control on the grid side of the electrolyzer ki22

0.48

The output of photovoltaic power generation unit is shown in the Figure 6.

The temperature is set at 28℃ unchanged, the light intensity is 0W/m2 for the first 10s, and the light intensity becomes 1200W/m2 in 10s. The power of the photovoltaic power generation unit is 0 for the first ten seconds. At ten seconds, due to the change of the light intensity, the power of the photovoltaic power generation unit becomes 0.3MW.


Figure 3. Wind power unit operation
Figure 4. Operation of wind turbine side converter
Figure 5. Operation of wind turbine grid side converter
Figure 6. Illumination change and photovoltaic power generation unit power output
Figure 7. Photovoltaic characteristic curve
Figure 8. Operation of the inverter of the photovoltaic power generation unit

Figure 7 presents the photovoltaic characteristic curves of the photovoltaic cells used in this paper. In this paper, the maximum power point tracking control method is adopted to ensure that photovoltaic cells are always close to the maximum power. The maximum power point is marked in the figure.

The operation of the photovoltaic converter is shown in the Figure 8.

In the first 10s, since the output power of the photovoltaic power generation unit is 0, the d-axis current and q-axis current of the inverter are both 0, and the inverter is turned off. At 10s, the photovoltaic power generation unit emits power, the reference current of the d-axis of the inverter is -0.4kA, the reference value of the q-axis current is 0.4kA, and the actual values of the d-axis and q-axis current fluctuate around the reference value, which can prove that the photovoltaic power generation unit is replaced. The flow device is turned on and off normally, and the control parameters and control strategies are reasonable and effective.

The output of the battery pack is shown in the Figure 9.

For the first 4s, the battery pack is in a discharge state, and the output power is 200kW to supplement the load demand. Since the battery pack is already running at rated power, the lack of power is supplemented by the grid. During 4-7s, the battery is working in the charging state, consuming 100kW of surplus wind power, and the rest of the wind power is consumed by the electrolyzer. During 7-10s, the battery is in discharge state, and the power shortage is 200kW.

Figure 9. Operation of the battery pack
Figure 10. Operation of the battery pack converter

The operation of the battery pack converter is shown in the Figure 10. The switching of different states of the battery pack is determined by whether its rated power is greater than the difference between wind power, photovoltaic and grid side loads. For details, see the energy management strategy section above.

The d-axis and q-axis currents of the battery converter are both maintained at around 0kA, which is consistent with the reference value, and the fluctuation level is small. Between 1.1kV and 0.9kV, it can be verified that the battery converter operates normally.

The operation of the electrolyzer and hydrogen storage tank is shown in the Figure 11.

Figure 11. Operation of electrolyzer and hydrogen storage tank

The 0-4s and 7-10s systems have no surplus power, and the electrolyzer does not produce hydrogen. The 4-7s and 10-15s electrolyzers consume 200kW of surplus power and produce 1.4mol/s of hydrogen. The initial pressure of the hydrogen storage tank is about 2.49483Mpa, and hydrogen is added at 4s-7s and 10-15s, and the pressure of the hydrogen storage tank remains unchanged for the rest of the time. The action of the electrolyzer and the hydrogen storage tank is consistent, which can verify the normal operation of the control of the hydrogen production and hydrogen storage systems.

The operation of the electrolytic cell converter is shown in the Figure 12.

The electrolytic cell was opened and operated at 4-7s and 10-15s. During the operation, the d-axis current and the q-axis current followed the reference value, and the inverter control was operating normally.

The power coordination control of the system is shown in Figure 13.

Figure 12. Operation of the electrolytic cell converter
Figure 13. Coordinated operation of system power

In the first 4s of the system, the output power of the wind turbine is 300kW, the photovoltaic has no output, and the rated power of the battery is 200kW, and the insufficient part is supplemented by the grid. The 4-7s wind turbine runs at the rated wind speed, the output power is 900kW, the battery consumes 100kW of surplus wind power, the electrolyzer consumes 200Kw of surplus wind power, and the photovoltaic has no output. The output power of the 7-10s wind turbine is 400kW, the battery supplements the shortfall power of 200kW, the photovoltaic has no output, and the electrolyzer does not operate. The output power of the 10-15s wind turbine is 600kW, which has met the load demand of the grid. The photovoltaic power generation is 300kW, and the electrolyzer consumes the surplus photovoltaic power generation of 200kW, and the battery consumes the surplus photovoltaic power generation of 100kW. It can be seen from Figure 13 that the energy conversion efficiency of the system established in this paper is high. Wind energy and solar energy can be better converted into electric energy, with less wind and light discarded. It can be fully consumed when wind energy and solar energy are abundant, and can be supplemented by the battery pack when wind power and photoelectric power are few.

5. Conclusion

In this paper, the mathematical model of the power generation system of wind power/photovoltaic/ hydrogen production/battery with common AC bus is constructed, and the energy coordination control strategy and the control strategy of each part of the converter are designed. Finally, the model is built in PSCAD/EMTDC, and the proposed simulation is verified. Based on the above theory and simulation results, the following conclusions can be drawn:

(1) The model constructed in this paper is reasonable and available. When the wind and photovoltaic power generation is surplus, the battery and electrolyzer run in time to absorb excess wind power and photovoltaic power generation, smooth the fluctuation of wind power generation and photovoltaic power generation, and verify the effectiveness and feasibility of the control strategy.

(2) Compared with the existing research, the research in this paper does not use a single wind power generation or photovoltaic power generation combined with energy storage to produce hydrogen, but uses wind and photovoltaic complementary power generation to produce hydrogen, which makes the advantages of the two energy sources complementary and better to ensure the stability of new energy power generation.

(3) In the follow-up research of this paper, fuel cells can be added, which can realize the power generation and utilization of hydrogen energy, and enhance the toughness of the system in the case of a large shortage of wind energy and light energy. Super capacitors can also be added to enhance the short-term power control capability of the system and improve the system robustness.

Funding
This paper was supported by Autonomous Region's major science and technology project (Grant No.: 2021ZD0027). “Key technologies for efficient integration and flexible control of high-power wind hydrogen storage systems”.
Data Availability

The data used to support the findings of this study are available from the corresponding author upon request.

Conflicts of Interest

The authors declare that they have no conflicts of interest.

References
1.
J. Wang, H. Li, and Y. Peng, “Application models of renewable energy under the carbon neutrality target,” Mod. Ch., vol. 42, no. 5, pp. 6-6, 2022. [Google Scholar]
2.
Y. Z. Wang, L. Kang, and J. Zhang, “Development history, typical form and future trend of integrated energy system,” Act. Energiae Solaris Sinica, vol. 42, no. 8, pp. 84-95, 2021. [Google Scholar]
3.
F. Cao, T. Guo, and A. Yin, “Research progress on design and energy management strategies of wind-solar-hydrogen hybrid power generation systems,” Distrib. Energy, vol. 6, no. 4, pp. 1-14, 2021. [Google Scholar]
4.
G. Cai, C. Chen, and L. Kong, “Modeling and control of wind power/photovoltaic/hydrogen production/supercapacitor grid-connected system,” Pow. Sys. Technol., vol. 40, no. 10, pp. 2982-2990, 2016. [Google Scholar]
5.
H. Kinoshita, R. Takahashi, T. Murata, J. Tamura, M. Sugimasa, A. Komura, and K. Ide, “A study of hydrogen generation with doubly-fed adjustable speed wind generator,” Electr. Eng. Jpn., vol. 175, no. 3, pp. 27-36, 2011. [Google Scholar] [Crossref]
6.
A. Abdelkafi and L. Krichen, “Energy management optimization of a hybrid power production unit based renewable energies,” Int. J. Elec. Power. Energy Syst., vol. 62, pp. 1-9, 2014. [Google Scholar] [Crossref]
7.
Y. Lu, C. Chen, and L. Liang, “Modeling and control of wind-hydrogen coupled system based on electric-hydrogen hybrid energy storage,” Mag. Introduct., vol. 48, no. 3, pp. 8-8, 2020. [Google Scholar]
8.
H. Zhang, Q. Sun, and Z. Li, “Research on cooperative control power generation strategy of wind-hydrogen coupling system,” J. Northeast Dian li Univ., vol. 38, no. 3, pp. 15-23, 2018. [Google Scholar]
9.
R. Maamouri, D. Guilbert, M. Zasadzinski, and H. Rafaralahy, “Proton exchange membrane water electrolysis: Modeling for hydrogen flow rate control,” Int. J. Hydrogen. Energ., vol. 46, no. 11, pp. 7676-7700, 2021. [Google Scholar] [Crossref]
10.
H. Deng, J. Chen, and Y. Teng, “Research on energy management strategy of wind-hydrogen coupling system,” Act. Energiae Solaris Sinica, vol. 42, no. 1, pp. 256-263, 2021. [Google Scholar]
11.
H. Sun, Z. Li, and A. Chen, “Status quo and development trend of wind power hydrogen production technology,” T. China Electrotechnical Soc., vol. 34, no. 19, pp. 4071-4083, 2019. [Google Scholar]
12.
H. Deng, J. Chen, and D. Jiao, “Energy management control strategy of wind-hydrogen coupled grid-connected system,” High Voltage Eng., vol. 8, no. 1, pp. 99-106, 2020. [Google Scholar]
13.
J. Wang, H. Li, and Y. Peng, “PEMFC modeling and performance analysis control,” Elect. Meas. Technol., vol. 45, no. 8, pp. 8-8, 2022. [Google Scholar]
14.
X. Guo, Y. Wei, and Y. Wan, “Overview of new energy hydrogen production power electronic converters,” Automat. Electr. P. Sys., vol. 45, no. 20, pp. 15-15, 2021. [Google Scholar]
15.
L. Kong, “Research on optimal configuration and coordinated control strategy of wind-solar-hydrogen integrated energy system,” Academic Dissertation, North China Electric Power University, Beijing, China, 2017. [Google Scholar]
16.
M. S. Fathy, H. Awad, H. Hegarzy, and E. E. Elkholy, “Performance of a PV-wind hybrid system under severe weather and loading conditions,” Int. J. Ind. Elec. Drive., vol. 4, no. 3, pp. 145-154, 2018. [Google Scholar] [Crossref]
17.
E. Ribeiro, A. J. M. Cardoso, and C. Boccaletti, “Power converters analysis in a renewable energy based hybrid system with hydrogen storage,” In IET Conference on Renewable Power Generation, (RPG 2011), Edinburgh, September 6-8, 2011, IET, pp. 1-6. [Google Scholar] [Crossref]
18.
J. P. Torreglosa, P. García, L. M. Fernández, and F. Jurado, “Energy dispatching based on predictive controller of an off-grid wind turbine/photovoltaic/hydrogen/battery hybrid system,” Renew. Energ., vol. 74, pp. 326-336, 2015. [Google Scholar] [Crossref]
19.
Z. Abdin and W. Mérida, “Hybrid energy systems for off-grid power supply and hydrogen production based on renewable energy: A techno-economic analysis,” Energ. Convers. Manage., vol. 196, pp. 1068-1079, 2019. [Google Scholar] [Crossref]
20.
A. O. Haruni, M. Negnevitsky, M. E. Haque, and A. Gargoom, “A novel operation and control strategy for a standalone hybrid renewable power system,” IEEE T. Sustain. Energ., vol. 4, no. 2, pp. 402-413, 2012. [Google Scholar] [Crossref]

Cite this:
APA Style
IEEE Style
BibTex Style
MLA Style
Chicago Style
GB-T-7714-2015
Yuan, T. Z., Li, H., & Jia, D. (2022). Modeling and Control Strategy of Wind-Solar Hydrogen Storage Coupled Power Generation System. J. Intell Syst. Control, 1(1), 18-34. https://doi.org/10.56578/jisc010103
T. Z. Yuan, H. Li, and D. Jia, "Modeling and Control Strategy of Wind-Solar Hydrogen Storage Coupled Power Generation System," J. Intell Syst. Control, vol. 1, no. 1, pp. 18-34, 2022. https://doi.org/10.56578/jisc010103
@research-article{Yuan2022ModelingAC,
title={Modeling and Control Strategy of Wind-Solar Hydrogen Storage Coupled Power Generation System},
author={Tianze Yuan and Hua Li and Dong Jia},
journal={Journal of Intelligent Systems and Control},
year={2022},
page={18-34},
doi={https://doi.org/10.56578/jisc010103}
}
Tianze Yuan, et al. "Modeling and Control Strategy of Wind-Solar Hydrogen Storage Coupled Power Generation System." Journal of Intelligent Systems and Control, v 1, pp 18-34. doi: https://doi.org/10.56578/jisc010103
Tianze Yuan, Hua Li and Dong Jia. "Modeling and Control Strategy of Wind-Solar Hydrogen Storage Coupled Power Generation System." Journal of Intelligent Systems and Control, 1, (2022): 18-34. doi: https://doi.org/10.56578/jisc010103
Yuan T., Li H., Jia D.. Modeling and Control Strategy of Wind-Solar Hydrogen Storage Coupled Power Generation System[J]. Journal of Intelligent Systems and Control, 2022, 1(1): 18-34. https://doi.org/10.56578/jisc010103
cc
©2022 by the author(s). Published by Acadlore Publishing Services Limited, Hong Kong. This article is available for free download and can be reused and cited, provided that the original published version is credited, under the CC BY 4.0 license.